CC-Link Digital/Analog Conversion Unit Screw Terminal Block Type

Brand :
MITSUBISHI
Caution
Product Description
CC-Link compatible unit.
[Features]
· Capable of digital-analog conversions within a field network.
[Applications]
· Convenient for equipment connection in a field network.
CC-Link Digital-Analog Conversion Unit Screw Terminal Block Type: Type Specifications
CC-Link Digital-Analog Current Conversion Unit AJ65BT-64DAI
CC-Link Digital/Analog Voltage Conversion Unit AJ65BT-64DAV

AJ65BT-64DAI
- 4 channels
- Input (resolution): 0 to 4,000
- Output: 4 to 20 mA DC
- Conversion speed: 1 ms / 1 channel
- 2-piece terminal block type
- Number of occupied stations: 2

AJ65BT-64DAV
- 4 channels
- Input (resolution): -2,000 to 2,000
- Output: -10 to 10 V DC
- Conversion speed: 1 ms / 1 channel
- 2-piece terminal block type
- Number of occupied stations: 2
CC-Link Digital-Analog Conversion Unit AJ65SBT-62DA
CC-Link Digital/Analog Conversion Unit AJ65SBT2B-64DA

AJ65SBT-62DA
- 2 channels
- Input (resolution): 0 to 4,000, -4,000 to 4,000
- Output: -10 to 10 V DC, 0 to 20 mA DC
- Conversion speed: 1 ms / 1 channel
- Terminal block type
- Number of occupied stations: 1

AJ65SBT2B-64DA
- 4 channels
- Input (resolution): 0 to 12,000, -12,000 to 12,000, -16,000 to 16,000
- Output: -10 to 10 V DC, 0 to 20 mA DC
- Conversion speed: 200 µs / 1 channel
- 2-piece terminal block type
- Number of occupied stations: 1
CC-Link Digital-Analog Conversion Unit AJ65VBTCU-68DAVN

AJ65VBTCU-68DAVN
- 8 channels
- Input (resolution): 0 to 4,000, -4,000 to 4,000
- Output: -10 to 10 V DC
- Conversion speed: 1 ms / 1 channel
- Single-action Connector Type
- Number of occupied stations: 1 (Ver. 2) / 3 (Ver. 1)
CC-Link Digital-Analog Conversion Unit Screw Terminal Block Type: Common Specifications
| Ambient Operating Temperature | 0 to 55°C | ||
|---|---|---|---|
| Ambient Storage Temperature | -20 to 75°C | ||
| Ambient Operating Humidity | 10 to 90% RH, assuming non-condensing | ||
| Ambient Storage Humidity | 10 to 90% RH, assuming non-condensing | ||
| Vibration Resistance | JIS B 3502, IEC 61131-2 Compatible | Under Intermittent Vibration | AJ65BT-64DAI, AJ65BT-64DAV, AJ65SBT-62DA Frequency: 5 to 8.4 Hz, amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z AJ65SBT2B-64DA Frequency: 5 to 8.4 Hz, Single amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z AJ65VBTCU-68DAVN Frequency: 5 to 9 Hz, Single amplitude: 3.5 mm Frequency: 9 to 150 Hz, Constant acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z |
| Under Continuous Vibration | AJ65BT-64DAI, AJ65BT-64DAV, AJ65SBT-62DA Frequency: 5 to 8.4 Hz, Amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Acceleration: 4.9 m/s2 AJ65SBT2B-64DA Frequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m/s2 AJ65VBTCU-68DAVN Frequency: 5 to 9 Hz, Single amplitude: 1.75 mm Frequency: 9 to 150 Hz, Constant acceleration: 4.9 m/s2 | ||
| Impact Resistant | JIS B 3502, IEC 61131-2 compatible (147 m/s2, 3 times in 3 directions of X, Y and Z) | ||
| Operating Atmosphere | No corrosive gas | ||
| Operating Altitude | 0 to 2,000 m | ||
| Installation Location | Inside the control panel | ||
| Overvoltage Category | II or lower | ||