Current Transformer (CT) CW-LT Series

Brand :
MITSUBISHI
Caution
- Some products are scheduled to be discontinued from October 2021. Depend on stock status, the end time will be changed. Please check the quotation and order screen for details.
Product Description
CW-□L series low voltage current transformer for voltages of 1,100 V or less.
[Features]
· For small current flows. Primary wind type.
· The direction of the attached legs can be changed 90°.
· Secondary terminal insulation caps are available as an option.
· Material with excellent insulation.
[Applications]
· Low voltage current transformer.
· For general meters.
Low Voltage Current Transformer Features

For small current flows / primary wind type.
The direction of the attached legs can be changed 90°.
Secondary terminal insulation caps are available as an option.
For general meters.
Self-Loading VA
| CW-5LP | CW-15LP | CW-40LP | |
|---|---|---|---|
| Self-loading (VA) | 3.5 (30 A or less) 5.0 (40, 50 A ) | 5.0 | 6.5 |
Low Voltage Current Transformer Specifications
| Type Name | Rated Primary Current (A) | Rated Load (VA) | Accuracy Grade (Class) | Excess Current Strength (Multiple) | Maximum Voltage /Withstand Voltage (kV) | Frequency (Hz) | External Diagram | Mass (kg) | Testing Advisability | |
|---|---|---|---|---|---|---|---|---|---|---|
| Secondary Current 5 A | Secondary Current 1 A | |||||||||
| CW-5LP | 1 | 1 | 5 | 1.0 | 40 | 1.15/ 4/- | 50/60 Both | Figure 1 | 0.7 | No |
| 2 | 2 | |||||||||
| 3 | 3 | |||||||||
| 5 | 5 | |||||||||
| 7.5 | 7.5 | |||||||||
| 10 | 10 | |||||||||
| 15 | 15 | |||||||||
| 20 | 20 | |||||||||
| 25 | 25 | |||||||||
| 30 | 30 | |||||||||
| 40 | 40 | Figure 2 | 1.1 | |||||||
| 50 | 50 | |||||||||
| CW-15LP | 1 | 1 | 15 | 1.0 | 40 | 1.15/ 4/- | 50/60 Both | Figure 2 | 1.1 | |
| 2 | 2 | |||||||||
| 3 | 3 | |||||||||
| 5 | 5 | |||||||||
| 7.5 | 7.5 | |||||||||
| 10 | 10 | |||||||||
| 15 | 15 | |||||||||
| 20 | 20 | |||||||||
| 25 | 25 | |||||||||
| 30 | 30 | |||||||||
| 40 | 40 | |||||||||
| 50 | 50 | |||||||||
| CW-40LP | 1 | 1 | 40 | 1.0 | 40 | 1.15/ 4/- | 50/60 Both | Figure 2 | 1.1 | |
| 2 | 2 | |||||||||
| 3 | 3 | |||||||||
| 5 | 5 | |||||||||
| 7.5 | 7.5 | |||||||||
| 10 | 10 | |||||||||
| 15 | 15 | |||||||||
| 20 | 20 | |||||||||
| 25 | 25 | |||||||||
| 30 | 30 | |||||||||
| 40 | 40 | 1.2 | ||||||||
| 50 | 50 | |||||||||
External Dimensions Diagram
Figure 1. CW-5LP Type (1 to 30 A)

Figure 2. CW-5LP (40, 50 A), CW-15LP, CW-40LP Type