Molded Case Circuit Breakers (MCCB) NF-HRV Series

Caution
Product Description
- MCCB (Molded Case Circuit Breakers) High performance class NF-HRV series from Mitsubishi electric. - Frame size is 50. - No. of pole can be select 2 or 3 poles. - Applicable for both AC/DC. - Rated ambient temperature 40°C. - Rated current can be select up to 50 A. - Rated insulation voltage (Ui) is 690 V - Mechanical duration (On/Off) is up to 25,000 times. - Electrical duration (On/Off) is up to 10,000 times. - Possible to reverse connection.
MITSUBISHI Circuit Breakers Specifications of MCCB
MITSUBISHI Circuit Breakers Specifications of NF63-HV
| Type Name Circuit Breakers | NF63-HV Circuit Breakers | |||||
|---|---|---|---|---|---|---|
| Rated current In A Standard ambient temperature 40°C (45°C for marine) | 10 15 20 30 40 50 | |||||
| Number of Positions | 2 | 3 | 4 | |||
| Rated Insulation Voltage Ui V | 690 | |||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | 2.5/2.5 | ||
| 500 V | 7.5/7.5 | |||||
| 440 V | 10/8 | |||||
| 415 V | 10/8 | |||||
| 400 V | 10/8 | |||||
| 380 V | 10/8 | |||||
| 230 V | 25/19 | |||||
| DC | 250 V (*1) | 7.5/7.5 | ||||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 10/8 | |||
| 400 V | 10/8 | |||||
| 380 V | 10/8 | |||||
| 230 V | 25/19 | |||||
| DC | 250 V | 7.5/7.5 | ||||
| NK (Icu/Ics) | AC | 450 V | 10/8 | - | ||
| 240 V | 25/19 | - | ||||
| DC | 250 V | 7.5/7.5 | - | |||
*: Circuit Breakers For 3-position and 4-position products, use 2 positions.

Internal equipment of NF63-HV

Temperature correction curve of NF63-HV
MITSUBISHI Circuit Breakers NF63-HRV/NF125-HV Specifications
| Type Name Circuit Breakers | NF63-HRV Circuit Breakers | NF125-HV Circuit Breakers | ||||||
|---|---|---|---|---|---|---|---|---|
| Rated current In A Standard ambient temperature 40°C (45°C for marine) | 15 20 30 40 50 | 15 20 30 40 50 | ||||||
| Number of Positions | 2 | 3 | 2 | 3 | 4 | |||
| Rated Insulation Voltage Ui V | 690 | 690 | ||||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | 2.5/1 | 10/8 | |||
| 500 V | 20/10 | 30/23 | ||||||
| 440 V | 30/15 | 50/38 | ||||||
| 415 V | 30/15 | 50/38 | ||||||
| 400 V | 30/15 | 50/38 | ||||||
| 380 V | 30/15 | 50/38 | ||||||
| 230 V | 85/43 | 100/75 | ||||||
| DC | 250 V (*1) | 40/20 | - | |||||
| GB 14048.2 (Icu/Ics) | AC | 415 V | - | 50/38 | ||||
| 400 V | - | 50/38 | ||||||
| 380 V | - | 50/38 | ||||||
| 230 V | - | 100/75 | ||||||
| DC | 250 V | - | - | |||||
| NK (Icu/Ics) | AC | 450 V | 30/15 | 50/38 | - | |||
| 240 V | 85/43 | 100/75 | - | |||||
| DC | 250 V | 40/20 | - | - | ||||
| Parts included as standard (Surface type) | Mounting screw M4 × 0.7 × 55 (2, 3-position 2 pcs., 4-position 4 pcs.) (*2) Insulation barrier (2-position 1 pc., 3-position 2 pcs., 4-position 3 pcs.) | |||||||
*1: Circuit Breakers For 3-position and 4-position products, use 2 positions. In that case, do not use the neutral pole of the 4-position product. Also, if you connect as shown in the figure, you can use up to 400 V DC for3-position products and 500 V DC for 4-position products. Please refer to the catalog for more details.
*2: It is attached to NF63-HRV and NF125-HV.

Internal equipment of NF63-HRV/NF125-HV
* Circuit Breakers For 2-position products of NF63-HRV and NF125-HV, refer to the number of mounting of 3-position products.

Temperature correction curve of NF63-HRV/NF125-HV
MITSUBISHI Circuit Breakers NF125-HEV Specifications
| Type Name Circuit Breakers | NF125-HEV Circuit Breakers | ||||
|---|---|---|---|---|---|
| Rated current In A Standard ambient temperature 40°C | 50 | ||||
| Number of Positions | 3 | 4 | |||
| Rated Insulation Voltage Ui V | 690 | ||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | 10/8 | |
| 500 V | 50/38 | ||||
| 440 V | 65/65 | ||||
| 415 V | 70/70 | ||||
| 400 V | 75/75 | ||||
| 380 V | 75/75 | ||||
| 230 V | 100/100 | ||||
| DC | 250 V | - | |||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 70/70 | ||
| 400 V | 75/75 | ||||
| 380 V | 75/75 | ||||
| 230 V | 100/100 | ||||
| DC | 250 V | - | |||
| NK (Icu/Ics) | AC | 450 V | - | ||
| 240 V | - | ||||
| DC | 250 V | - | |||
| Parts included as standard (Surface type) | Circuit Breakers, Mounting screw M4 × 0.7 × 55 (3-position 2 pcs., 4-position 4 pcs.) Insulation barrier (3-position 4 pcs., 4-position 6 pcs.) | ||||

Internal equipment of NF125-HEV
(*) SLT is included from the standard. A control power supply (100 to 240 V AC/DC) is required.
Current reduction curve of NF125-HEV
*Please refer to the catalog for any information not listed above.