Miniature Circuit Breakers BH Series

Brand :
MITSUBISHI
Caution
Product Description
WS-V series BH type no-fuse breaker.
[Features]
· Product lineup includes BH-K with agreed dimensions for electric light power distribution boards, and BH-P for insertion connection.
· Series expanded and models renewed from 30 A frames to 1,600 A frames.
[Applications]
· Breaker for power distribution board.
BH-C1/BH-C2 Characteristics and External Shape
BH-C1/BH-C2 Specifications
| Model | BH-C1 | BH-C1D | BH-C2 | BH-C2D | ||
|---|---|---|---|---|---|---|
| No. of poles / elements | 2P1E | 2P2E | ||||
| Rated current (A) | 15 20 30 | |||||
| Rated insulation voltage (V) | 265 | |||||
| Rated breaking capacity JIS C 8201-2-1 Ann.2 kA | AC | 100 V | 5 | 5 | - | - |
| 100/200 V | - | - | 5 | 5 | ||
| 240 V | - | - | 2.5 | 2.5 | ||
| 125 V DC | - | 1 | - | 2.5 | ||
| Connection method on power supply side | Screw terminal | Suitable | Suitable | Suitable | Suitable | |
| Plug-in terminal (AP) (*2) | Possible use | - | Possible use | - | ||
| Connection method on load side | Screw terminal | Suitable | Suitable | Suitable | Suitable | |
| Quick-connect terminal (QT) (*1) | Suitable | - | Suitable | - | ||
*1: When ordering a quick-connect terminal (QT), please specify "QT" in your order.
*2: When ordering a plug-in terminal (AP), please specify "AP" in your order.
Operating Characteristics Curve

Temperature Correction Curve

BH-C1/BH-C2 Drawing

Screw terminal

Quick-connect terminal (QT)
BH-CP1/BH-CP2 Characteristics and External Shape
BH-CP1/BH-CP2 Specifications
| Model | BH-CP1NR | BH-CP1NT | BH-CP2 | ||
|---|---|---|---|---|---|
| No. of poles / elements | 2P1E | 2P2E | |||
| Rated current (A) | 15 20 30 | ||||
| Rated insulation voltage (V) | 265 | ||||
| Rated breaking capacity JIS C 8201-2-1 Ann.2 kA | AC | 100 V | 5 | - | |
| 100/200 V | - | 5 | |||
| 240 V | - | 2.5 | |||
| Connection method on load side | Screw terminal | Suitable | Suitable | Suitable | |
| Quick-connect terminal (QT) (*1) | Suitable | Suitable | Suitable | ||
Operating Characteristics Curve

Temperature Correction Curve

BH-CP1/BH-CP2 Drawing
BH-K Characteristics and External Shape
BH-K Specifications
| Model | BH-K | |||||
|---|---|---|---|---|---|---|
| Rated current (A) | 10 15 20 30 40 50 | 15 20 30 40 50 | ||||
| Number of poles | 1 | 2 | 3 | |||
| Rated insulation voltage (V) | 300 | 500 | ||||
| Rated breaking capacity (kA) | JIS C 8201-2-1 Ann.2 | AC | 100 V | 5 | - | |
| 100 V / 200 V | - | (*1) (5) | - | |||
| 200 V | - | 5 (*1) (-) | ||||
| 240 V | 2.5 | (*1) (2.5) | - | |||
| 415 V | - | 2.5 (*1) (-) | ||||
| DC | 125 V | 1 | 5 | |||
| NK (*2) | AC | 125 V | - | 7.5 | 5 | |
| 250 V | - | 5 | 2.5 | |||
| DC | 125 V | - | 5 | 2.5 | ||
*1: Values in ( ) are for a rated current of 10 A.
*2: Please specify if NK standard is required.
Operating Characteristics Curve

Temperature Correction Curve

Drawing