MELSEC-QS Series CC-Link Safety Input/Output

Brand :
MITSUBISHI
Caution
Product Description
- CC-Link Safety Remote I/O modules, Terminal block type, MELSEC-QS Series from MITSUBISHI.
- 2 terminal block types available, Screw terminal block type and Spring clamp terminal block type.
- The system complying with Category 3 or Category 4 of EN 954-1 can be configured by the combination of wiring and parameters.
- Rated input voltage: 24 V DC
- Ingress protection level: IP2X
- The remote I/O module which has obtained the highest safety level applicable to programmable controllers, and the safety-related system with high security can be configured.
MELSEC-QS Series CC-Link Safety, Safe Input/Output Specifications
QS0J65BTB2-12DT-K

QS0J65BTB2-12DT-K image
QS0J65BTB2-12DT-K Performance Specifications
| Input Specifications | ||
|---|---|---|
| Number of Inputs | 8 (for duplexing input) 16 (for single output) | |
| Rated Input Voltage | 24 V DC (ripple ratio within 5%) (allowable voltage range from 19.2 to 28.8 V DC) | |
| Rated Input Current | Approx. 4.6 mA | |
| Maximum Number of Simultaneous Input Points | 100% | |
| ON Voltage / ON Current | 15 V DC or more / 2 mA or more | |
| OFF Voltage / OFF Current | 5 V DC or less / 0.5 mA or less | |
| Input Resistance | Approx. 5.6 kΩ | |
| Input Format | DC input (negative common type) | |
| Input Response Time | OFF > ON | 0.4 ms or less (24 V DC) |
| ON > OFF | 0.4 ms or less (24 V DC) | |
| Safety Remote Station Input Response Time | 11.2 ms or less + denoising filter time (1 ms, 5 ms, 10 ms, 20 ms, 50 ms) | |
| Input Common Method | 16 points 1 common (terminal block model, 2-wire type) | |
| Input Insulation Method | Opto-isolator insulation | |
| Output Specifications | ||
| Number of Outputs | 4 points (when selecting source + sink type) 2 points (when selecting source + source type) | |
| Rated Load Voltage | 24 V DC | |
| Operating Load Voltage Range | 19.2 to 28.8 V DC (Ripple ratio within 5%) | |
| Maximum Load Current | 0.5 A / 1 point | |
| Maximum Inrush Current | 1.0 A, 10 ms or less | |
| Leakage Current When OFF | 0.5 mA or less | |
| Maximum Voltage Drop When ON | 1.0 V DC or less | |
| Protection Function | Output Overload Protection Function | |
| Output Format | Source + sink type Source + source type | |
| Output Response Time | OFF > ON | 0.4 ms or less (24 V DC) |
| ON > OFF | 0.4 ms or less (24 V DC) | |
| Safety Remote Station Output Response Time | OFF > ON | 11.2 ms or less |
| ON > OFF | 10.4 ms or less | |
| Surge Suppressor | Zener diode | |
| Output Common Method | 4 points 1 common (terminal block model, 2-wire type) | |
| Common Current | Maximum 4 A (total of input and output) | |
| Output Insulation Method | Opto-isolator insulation | |
| Common Specifications | ||
| Dielectric Strength | Between all DC external terminals as a whole and the earth: 500 V AC for 1 minute | |
| Insulation Resistance | Between all DC external terminals as a whole and the earth: 10 MΩ or more at 500 V DC on an ohmmeter | |
| Protection Grade | IP2X | |
| Station Type | Safety remote I/O station | |
| Number of Occupied Stations | 1 | |
| Number of Accesses to the Non-volatile Memory Inside the Unit | 1012 | |
| Safety Remote Station Refresh Response Process Time | 9.6 ms | |
| External Power Supply | Voltage | 19.2 to 28.8 V DC (Ripple ratio within 5%) |
| Current | 60 mA (for 24 V DC and with all points ON, not including external load current) | |
| Protection Function | External supply power overvoltage protection function, external supply power overcurrent protection function | |
| Fuse | 8 A (non-replaceable) | |
| Unit Power Supply | Voltage | 19.2 to 28.8 V DC (Ripple ratio within 5%) |
| Current | 140 mA or less (24 V DC, with all points are ON) | |
| Protection Function | Unit power supply overvoltage protection function, unit power supply overcurrent protection function | |
| Fuse | 0.8 A (non-replaceable) | |
| Allowable Momentary Power Loss Time | Within 10 ms | |
| External Wiring Connection Method | Communication part, unit power supply part: 7-point 2-piece terminal block (M3 screw) Input/output power supply, input/output part: 18-point 2-piece terminal block (M3 screw) x 3 | |
| Weight | 0.71 kg | |
QS0J65BTB2-12DT-K General Specifications
| Ambient Operating Temperature | 0 to 55°C | ||
|---|---|---|---|
| Ambient Storage Temperature | -40 to 75°C | ||
| Ambient Operating Humidity | 5 to 95% RH, assuming non-condensing | ||
| Ambient Storage Humidity | 5 to 95% RH, assuming non-condensing | ||
| Vibration Resistance | JIS B 3502, IEC 61131-2 Compatible | Under Intermittent Vibration | Frequency: 5 to 8.4 Hz, Single amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z |
| Under Continuous Vibration | Frequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m/s2 | ||
| Impact Resistant | JIS B 3502, IEC 61131-2 compatible (147 m/s2,for a duration of 11 ms, 3 times in 3 directions of X, Y and Z with a half-sine pulse) | ||
| Operating Atmosphere | No Corrosive Gas | ||
| Operating Altitude | 0 to 2,000 m | ||
| Installation Location | Inside the control panel | ||
| Overvoltage Category | II or lower | ||
| Pollution Degree | 2 or less | ||
| Equipment Class | Class III | ||