CC-Link Master/Local Station Interface Board For PC

Caution
Product Description
CC-Link master/local station interface board for PC.
[Features]
· Master station supporting CC-Link Ver.2. Can be used as a standby master station or local station.
· Also supports dual-core processors and multi-CPU configuration PCs.
· Device data of the sequencer can be collected/written from Excel just by simple setting.
[Applications]
· Convenient for connecting equipment over a field network.
Interface Board for PC Features
Supports PCI Express Bus and Microsoft Windows Server 2003 R2
- Supporting PCI Express bus and Microsoft Windows Server 2003 R2 enables a wider selection of PCs in a CC-Link system.
- Also supports dual-core processors and multi-CPU configuration PCs.
Simple Logging in Excel
By using MX Component and MX Sheet, device data of the sequencer can be collected/written from Excel with only simple settings, and without any programming.
Simple Programming With Microsoft Visual Basic and Microsoft Visual C++
Functions supporting Microsoft Visual Basic and Microsoft Visual C++ allow simple creation of user programs such as remote RUN/STOP/PAUSE of the sequencer CPU, or reading/writing of devices.
Interface Board for PC Specifications
| Model | Q80BD-J61BT11N | Q81BD-J61BT11 |
|---|---|---|
| Station type | Master station, standby master station or local station | |
| Number of occupied stations (for local station) | 1 to 4 stations (switch by utility parameter settings) | |
| Number of boards that can be installed | Maximum 4 boards*1 | |
| Mounting slot | PC PCI bus slot (half size) | PC PCI Express X1, X2, X4, X8, X16 slot (half size) |
| Number of occupied slots | 1 slot | |
| Current consumption (5 V DC) | 0.56 A | - |
| Current consumption (3.3 V DC) | - | 1.06 A |
| External dimensions | 153 (W) × 121 (H) × 19 (D) mm | |
| Weight | 0.11 kg | |
*1: CC-Link Ver. 2 boards and Ver. 1 boards (A80BD-J61BT11/13) cannot be used together on the same PC.
Interface Board for PC Drawing

Model Q80BD-J61BT11N

Model Q81BD-J61BT11
CC-Link Ver. 2 Utility
The following functions can be used by CC-Link Ver. 2 Utility.
Board information display, circuit monitoring (other stations), memory / I/O diagnostics, testing, parameter setting and other-side setting for multi-CPU PC communication, etc.
Device Monitor Utility
The following functions can be used by the Device Monitor Utility.
Batch monitoring / 16 point registration monitoring, and change of device values.
User’s Manual
Installed with User's Manual (PDF) in Japanese and English.