Solid State/Timer H3RN

Caution
Product Description
[Features]
· Type G2R A small scale and thin timer which is relay and pin compatible.
· Implements multiple time ranges and operational modes.
· A small thin size which contributes to space saving.
· UL, CSA standard acquired.
· Meets the EN61812-1 standard.
· Corresponds to the CE mark.
Solid-State Timer H3RN Specifications

H3RN-2 external appearance

H3RN-2 external appearance

H3RN-1, H3RN-11 outline drawing

H3RN-1, H3RN-11 dimensional outline drawing, units: mm
Note. For the connection socket, use the P2RF-05-E surface connection socket or P2R-057P rear surface connection socket.

H3RN-2 outline drawing

H3RN-2 dimensional outline drawing, units: mm
Note: For the connection socket, use the P2RF-08-E surface connection socket or P2R-087P rear surface connection socket.

Dimensional drawing when socket is mounted, units: mm
- *1 The value when using a PFP-□N support rail with P2RF-05-E. It is +9 mm when using PFP-□N2.
- *2 The value when using a PFP-□N support rail with P2RF-08-E. It is +9 mm when using PFP-□N2.
Note: There are no restrictions on the mounting direction.

Dimensional drawing when socket is mounted, units: mm
| Item | Format | ||
|---|---|---|---|
| Series H3RN-1/-2 | Series H3RN-11/-21 | ||
| Time Specifications | Short time type 0.1 s to 10 min (4 range switching; 1 s, 10 s, 1 min, 10 min) | Long time type 0.1 min to 10 h (4 range switching; 1 min, 10 min, 1 h, 10 h) | |
| Power Supply Voltage*2 | · 24 V AC, 50/60 Hz · 12 V DC · 24 V DC | ||
| Operation Mode | Can switch between 4 modes: ON delay, interval, start flicker OFF and start flicker ON, using the DIP switch | ||
| Allowable Voltage Variation Range | 85 to 110% of power supply voltage (however, 90 to 110% of power supply voltage for 12 V DC specifications)*1 | ||
| Power Consumption (Reference) | 24 V AC | When Relay ON, 0.8 VA | |
| 24 V DC | When Relay ON, 0.5 W | ||
| 12 V DC | When Relay ON, 0.4 W | ||
| Recovery Voltage | 10% or less of power supply voltage | ||
| Control Output | 250 V AC 3 A resistive load (cosφ = 1) (using G6B-2□14P-FD-US [contact material: AgSnIn]) Minimum applied load: 5 V DC 10 mA (P level, reference value) | ||
| Ambient Operating Temperature | -10 to +55°C (No Freezing) | ||
| Storage Temperature | -25 to +65°C (No Freezing) | ||
| Ambient Operating Humidity | 35 to 85% | ||
*1 When continuously using at an ambient operating temperature of 50°C or more, use at 90 to 110% of the power supply voltage (95 to 110% for 12 V DC).
*2 When using the AC 2-wire proximity sensor and timer in combination, refer to "Common Timer Precautions ● Power Supply."
*Refer to the catalog for specifications other than those listed above.