Power Solid State Relay G3PA

Caution
Product Description
[Features]
· Ultra small slim type with integrated radiator.
· Withstand voltage AC4,000V.
· Miniaturization due to optimal radiator design.
· In addition to screw mounting, DIN rail mounting is also possible.
· Close contacted mounting can be easily done at the connection terminal, and is even applicable in three-phase incapable models (there is no connection terminal in models G3PA-260B-VD, and G3PA-450B-VD-2).
· Even if the power element breaks, the cartridge format allows for it to be replaced.
· UL, CSA standards, EN standards (VDE certification) acquired.
· -VD (rating 200V) type received the rating for its strengthened insulation (VDE).
Specification Table of OMRON Solid State Relay

Appearance of Solid State Relay G3PA

External dimensions and mounting hole dimensions of Solid State Relay model G3PA-210B-VD

External dimensions and mounting hole dimensions of Solid State Relay model G3PA-220B-VD

External dimensions and mounting hole dimensions of Solid State Relay model G3PA-240B-VD

External dimensions of Solid State Relay Model G3PA-420B-VD and Model G3PA-420B-VD-2, mounting hole dimensions, terminal arrangement/internal connections

External dimensions of Model G3PA-430B-VD and Model G3PA-430B-VD-2, mounting hole dimensions, terminal arrangement/internal connections

External dimensions of Model G3PA-260B-VD and Model G3PA-450B-VD-2, mounting hole dimensions, terminal arrangement/internal connections
OMRON Solid State Relay Rating (Input * Ambient Temperature 25℃)
| Rated voltage | Operating voltage range | Solid State Relay Input current *1 | Voltage Levels | |
|---|---|---|---|---|
| Operating voltage | Recovery Voltage | |||
| Solid State Relay DC5-24V | DC4~30V | 7mA or less *2 | DC4V or less | DC 1V or higher |
| DC12-24V | DC9.6~30V | DC9.6V or less | ||
*1. The input current of the Solid State Relay G3PA is constant (at an ambient temperature of 25°C).
*2. Up to three Omron Thermac series DC12V, 20mA output types can be connected.
Rated of OMRON Solid State Relay (Output)
| Solid State Relay format | Rated Load Voltage | Load Voltage Range | Load current *1 | Surge current resistance | Peak repetitive off-state voltage (reference value) |
|---|---|---|---|---|---|
| Solid State Relay Model G3PA-210B-VD | AC24-240V (50/60Hz) | AC19-264V (50/60Hz) | 0.1 to 10A (at 40°C) | 150A (60Hz, 1 cycle) | 600V (VDRM) |
| Solid State Relay Model G3PA-220B-VD | 0.1 to 20A (at 40°C) | 220A (60Hz, 1 cycle) | |||
| Model G3PA-240B-VD | 0.5 to 40A (at 40°C) | 440A (60Hz, 1 cycle) | |||
| Model G3PA-260B-VD | 0.5 to 60A (at 40°C) | 440A (60Hz, 1 cycle) | |||
| Model G3PA-420B-VD | AC180-400V (50/60Hz) | AC150-440V (50/60Hz) | 0.5 to 20A (at 30°C) | 220A (60Hz, 1 cycle) | 1,000V (VDRM) |
| Model G3PA-430B-VD | 0.5 to 30A (at 30°C) | 440A (60Hz, 1 cycle) | |||
| Model G3PA-420B-VD-2 | AC200-480V (50/60Hz) | AC180-528V (50/60Hz) | 0.5 to 20A (at 30°C) | 220A (60Hz, 1 cycle) | 1,200V (VDRM) |
| Model G3PA-430B-VD-2 | 0.5 to 30A (at 30°C) | 440A (60Hz, 1 cycle) | |||
| Model G3PA-450B-VD-2 | 0.5 to 50A (at 30°C) | 440A (60Hz, 1 cycle) | |||
*Depends on ambient temperature.
Performance of OMRON Solid State Relay
| Solid State Relay format | Model G3PA- 210B- VD | Model G3PA- 220B- VD | Model G3PA- 240B- VD | Model G3PA- 260B- VD | Model G3PA- 420B- VD | Model G3PA- 430B- VD | Model G3PA- 420B -VD-2 | Model G3PA- 430B -VD-2 | Model G3PA- 450B -VD-2 |
|---|---|---|---|---|---|---|---|---|---|
| Solid State Relay Operating time | 1/2 cycle of load power supply + 1 ms or less | ||||||||
| Recovery Time | 1/2 cycle of load power supply + 1 ms or less | ||||||||
| Output on voltage drop | 1.6V (RMS) or less | 1.8V (RMS) or less | |||||||
| Leakage current | 5mA or less (at AC100V) 10mA or less (at AC200V) | 10mA or less (at AC100V) 20mA or less (at AC200V) | 10mA or less (at AC200V) 20mA or less (at AC400V) | 20mA or less (at AC480V) | |||||
| Insulation resistance | 100MΩ or more (at DC500V mega) | ||||||||
| Withstand voltage | AC4,000V 50/60Hz 1min | ||||||||
| vibration | 10 to 55 to 10Hz Single amplitude 0.375mm (double amplitude 0.75mm) (when mounted on a DIN rail) | ||||||||
| Solid State Relay impact | 300m/s2(when mounted on a DIN rail) | ||||||||
| Storage temperature | -30 to +100°C (but no freezing or condensation) | ||||||||
| Ambient temperature | -30 to +80°C (but no freezing or condensation) | ||||||||
| Ambient humidity | 45~85%RH | ||||||||
| mass | Approx. 260g | Approx. 340g | Approx. 460g | Approximately 900g | Approx. 290g | Approx. 410g | Approx. 380g | Approximately 500g | Approximately 900g |
Installation Instructions of OMRON Solid State Relay

Solid State Relay SSR mounting interval
(In-panel mounting conditions)

Relationship between SSR and duct (duct depth)
Countermeasure example 1: Use a duct with a short depth.
Countermeasure example 2: If the duct cannot be shortened, provide a base (made of metal) to prevent the SSR from being covered by the duct.

Ventilation Solid State Relay method to outside the control panel
- * If the intake or exhaust port is equipped with a filter, clean it regularly to prevent a decrease in efficiency due to clogging.
- * Solid State Relay Do not place any objects that may obstruct the intake or exhaust of air around the inside or outside of the intake or exhaust vents.
- * When using a heat exchanger, it is considered more effective to install it in front of the SSR.