Small Digital Panel Meter K3GN

Brand :
OMRON
Caution
Product Description
[Features]
· A small digital panel meter with a small size of 48 (W) × 24 (H) × 83 (D) mm, suitable for smaller sized equipment control panels.
· Supports DC voltage/current and rotation pulse multi input.
· Switchable 2-color display of green/red.
· Output type is freely selectable.
· CE marking compliant.
· Certified under UL/CSA standards.
· Waterproof structure compliant with NEMA4X (IP66 equivalent).
Small Digital Panel Meter Specifications

K3GN external appearance

K3GN dimensional outline drawing

Panel machining dimensions
Mounting panel thickness: 1 to 5 mm.
Mount horizontally.
Handy type hydraulic puncher HP-2, dedicated replacement blade (HP-22.2-45K)
- *For installation, insert the K3GN panel into the rectangular hole, insert the adapter from the rear, and push it in to reduce the gap between the panel surface and the adapter. Secure the unit with screws.
- *For water-proof installation, insert the water-proof packing onto the body of the K3GN.
- *When mounting multiple units, make sure that the ambient temperature does not exceed specifications for this unit.
Rating
| Format | Series K3GN-ND DC Voltage / Current / NPN Input Type | Series K3GN-PD DC Voltage / Current / PNP Input Type | Series K3GN-NL Micro Voltage / NPN Input Type | |
|---|---|---|---|---|
| Power Supply Voltage | 24 V DC | |||
| Allowable Power Supply Voltage Range | 85 to 110% of power supply voltage | |||
| Power Consumption (At Maximum Load)* | 2.5 W or less (at DC maximum load: when all LEDs are ON) | |||
| Input Signal | DC voltage / current / non-voltage contact / open collector | |||
| DC Voltage / Current Input | A/D Conversion Method | Double Integral Method | ||
| Pulse Signal Input | Pulse Measurement Method | Periodic Measurement Method | ||
| External Power Supply | NA | |||
| Event Input | Current value hold or forced zero (select as desired) *Effective for DC voltage / DC input only. (Control Signal Minimum Input Time 80 ms) | |||
| Output (Differs Based On Model) | Relay Contact Output | 30 V DC 1 A (resistive load), mechanical life: 50 million operations or more, electrical life: 100,000 operations or more | ||
| Transistor Output | Maximum load voltage: 24 V DC, maximum load current: 50 mA, leak voltage: 100 μA or less | |||
| Communication Output | RS-485 (2 Wire Half Duplex) | |||
| Linear Output | DC current (DC 0 to 20 mA / DC 4 to 20 mA: load 500 Ω or less, resolution approx. 10,000) DC voltage (0 to 5 V DC / 1 to 5 V DC / 0 to 10 V DC: load 5 kΩ or more, resolution approx. 10,000) | - | DC current (DC 0 to 20 mA / DC 4 to 20 mA: load 500 Ω or less, resolution approx. 10,000) DC voltage (0 to 5 V DC / 1 to 5 V DC / 0 to 10 V DC: load 5 kΩ or more, resolution approx. 10,000) | |
| Display Method | Negative LCD (backlight LED) display, 7-segment digital display (character height PV: 7 mm) and single illuminated display | |||
| Main Functions | Scaling, pre-scaling, teaching, averaging processing, forced zero, display color switching, output type selection, key protect, start-up compensation timer, hysteresis | |||
| Operating Temperature Range | When In Use | -10 to +55°C (No Freezing Or Condensation) | ||
| When Stored | -25 to +65℃ (No Freezing Or Condensation) | |||
| Operating Humidity Range | When In Use | 25 to 85% RH | ||
| Height | 2,000 m or less | |||
| Accessories | Rubber packing, fixture, instruction manual | |||
- *A rated or higher control power supply capacity is required when powering ON. Be especially careful when using multiple units.
- *When turning ON the power, all indicators will be illuminated and will display the initial value, and all outputs will be in the OFF state.
- *When the start-up compensation timer is operating, the value "00000" indicating the unmeasured state is displayed and all outputs are in the OFF state.
- *Refer to the catalog for performance, input range, measurement range, measurement accuracy, and other functions.