UL standard lead-free heat resistant PVC insulated cable UL 1015 (including bobbin (reel) winding)

Brand :
MISAWADENSEN
Caution
Product Description
• Single core ductile cable UL1015 type / UL (Underwriters Laboratories Inc.) standard supported.
• Appliance Wiring Material UL 758 style 1015.
• 600V cable for general purposes.
• Operating temperature range is 0-105℃.
• 7 cable sizes are available AWG16, AWG18, AWG20, AWG22, AWG24, AWG26 and AWG28
• 12 Cable colors are available White, Black, Red, Blue, Yellow, Green, Sky blue, Orange, Brown, Gray, violet and Yellow/Green color.
• Can order cable for 4 sizes of length. (10m, 50m, 100m and 305m)
• Insulated cable PVC (Polyvinyl Chloride)
Product Specifications
- Specification Number: MSD-CU002
| Standard | Rated voltage | Rated temperature | Flame retardancy | Certification number | |
|---|---|---|---|---|---|
| UL | UL758 Style 1015 | 600V | 105℃ | VW-1 | E192340 |
| cUL | CSA C22.2 No. 210 | 600V | 105℃ | FT1/FT2 | |
| Flame retardant -F- mark | - | - F- | MDN | ||
- *Rated / applicable standards

Wire Surface Printing
Specifications Table
Structure and Electrical Properties
| Part number | Conductor size | Color | overall length (m) | Conductor | Insulator | Conductor resistance Ω/km or less (20℃) | Insulation Resistance MΩ/km or more (20℃) | Allowable current A (40℃) | Test voltage (V/min) | Approximate Weight (kg/km) | ||
| Configuration (pcs./mm) | Outer diameter (mm) | Thickness (mm) | Outer diameter (mm) | |||||||||
| UL1015 | 24* (0.2 mm²) | W (White) / BK (Black) R (Red) / BE (Blue) Y(yellow), GN (green) O (orange), BN (brown) H (Gray) GY (Green/Yellow, spiral) | 10 / 50 / 100 / 305 (1 roll) | 11/0.16 | 0.61 | 0.85 | 2.31 | 88.7 | 50 | 8.0 | AC.2000 | 7.6 |
| 22* (0.3 mm²) | 17/0.16 | 0.76 | 2.46 | 57.4 | 10.3 | 9.3 | ||||||
| 20* (0.5 mm²) | 21/0.18 | 0.95 | 2.65 | 36.8 | 13.4 | 11.8 | ||||||
| 18* (0.75 mm²) | 34/0.18 | 1.21 | 2.91 | 21.8 | 18.3 | 16.0 | ||||||
| 16* (1.25 mm²) | 26/0.26 | 1.53 | 3.23 | 13.7 | 24.4 | 22.1 | ||||||
| 14* (2.0 mm²) | 41/0.26 | 1.92 | 3.62 | 9.6 | 30.8 | 31.2 | ||||||
| 12 * (3.5 mm²) | 65/0.26 | 2.42 | 0.87 | 4.16 | 6.1 | 41.3 | 45.7 | |||||
| 10* (5.5 mm²) | 104/0.26 | 2.99 | 0.96 | 4.91 | 3.8 | 56.3 | 69.1 | |||||
*GY (Green/Yellow) is a green wire core with a yellow band (approximately 25% retention) and has a spiral specification.
GY (Green/Yellow) spiral

Current Reduction Factor
The allowable current value is a calculated value when 1 line is installed in the air at an ambient temperature of 30℃, and is not a guaranteed value.
If the ambient temperature is 30℃ or higher, multiply the allowable current by the above current reduction factor.
(Example) Allowable current value for 24 AWG and ambient temperature of 40℃
5 x 0.93 = 4.65 (A)
| Ambient temperature (℃) | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 |
| Current Reduction Factor | 0.97 | 0.93 | 0.89 | 0.86 | 0.82 | 0.77 | 0.73 | 0.68 | 0.63 | 0.58 | 0.52 | 0.45 | 0.37 | 0.26 | 0 |
If the ambient temperature is 30℃ or higher, multiply the allowable current by the above current reduction factor.
(Example) Allowable current value for 24 AWG and ambient temperature of 40℃
5 x 0.93 = 4.65 (A)
· Bending radius: Overall diameter x 8 times (fixed part only)
· The minimum operating temperature is 0℃. (Reference value)
Bobbin size AWG24 to AWG20
P-30 bobbin