Equipment Internal Wiring Wire and Supply Power Wire, UE/SSX84 LF

Caution
Product Description
[Features]
● Dual UL and cUL. (Category: AVLV2, AVLV8)
● UL VW-1 and cUL FT1 flame-retardancy compliant.
● Uses vinyl with excellent flexibility.
● Since the conductor is finely stranded, it has excellent flexibility and pliability.
● CE Marking Conformity Declaration Product (TUV certified product). (TUV Certificate No. J9950730)
● UE/SSX84 offers the ideal wiring for locations where electric wire hardness poses a problem, such as when fixing wiring, or in locations where R cannot be obtained etc.
● (Note 1. Per CSA standards, cannot be used for power supplies).
Compliant standard
| Certification | UL AWM | cUL AWM | TUV.CE marking | Electrical Appliances and Materials Safety Act of Japan |
|---|---|---|---|---|
| Applicable standards | UL 758 | CSA C22.2 No.210 | EN50525-2-31 | The Japanese ministerial ordinance specifying technical requirements for electrical appliances |
| Format symbol | UL STYLE 1283 1284 | CSA AWM I A/B | Equivalent to H07V-K | Synthetic resin Insulation cable |
| Rated Voltage | 600 V | 600 V | 450/750 V | 600 V |
| Rated temperature | 105°C | 105°C | 70°C | 60°C |
| Conductor | UL 758 | CSA C22.2 No.210 | EN60228 | JIS C 3102 |
| Flame Retardancy | VW-1 | FT1 | EN50264-2-1 | JIS C 3005 4.26.2 b |

Standard table

* In addition to the UL and CSA standard withstand voltage tests mentioned above, it has passed the 2,500 V / 5 min test.
* The allowable current value in the () is a reference value and for transport purpose only.
Product characteristics
Allowable current
- The allowable current is the value when single cable installed in air and the ambient temperature is 30°C.
- Multiply by the following correction factors according to the ambient temperatures, installation conditions, etc.
Current reduction coefficient (In case of ambient temperature)
| Ambient temperature (°C) | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 |
|---|---|---|---|---|---|---|---|---|
| Current reduction factor | 1.00 | 0.93 | 0.86 | 0.77 | 0.68 | 0.58 | 0.45 | 0.26 |
Current reduction coefficient (In the case of multi-row laying)
| Number of cables | 2 to 3 | 4 | 5 to 6 | 7 to 15 | 16 to 40 | 41 to 60 | 61 or more |
|---|---|---|---|---|---|---|---|
| Current reduction factor | 0.70 | 0.63 | 0.56 | 0.49 | 0.43 | 0.39 | 0.34 |
Transport property
| Bending | Winding | U-shaped folding | 90° flexing | Twisting | Transport bending | |
|---|---|---|---|---|---|---|
| Direct | Bending | |||||
| C | A | A | C | B | B | C |
* A to C in the table represent the following characteristics;
Number of tests A = 10 million or more / B = 5 million or more / C = 3 million or more / D = 1 million or more / E = 500,000 or more
Oil resistance
| Insulation oil | Lubricant oil | Cutting oil I | Cutting oil II | Hydraulic oil | Grease |
|---|---|---|---|---|---|
| C | C | C | C | C | C |
A: There is no practical problem at all. /B: There is little deterioration but almost no practical problem to use. /C: It shows a certain level of deterioration and may not be usable.
Wire core identification
Structural drawing

Surface printing
(1) For 1 to 3/0 AWG

(2) For 4/0 AWG

Identification
| — | AWG | Black | White | Red | Blue | Brown | Y/G |
|---|---|---|---|---|---|---|---|
| UE/ SSX 84 LF | 1 | ○ | — | — | — | — | ○ |
| 1/0 | ○ | — | — | — | — | ○ | |
| 2/0 | ○ | — | — | — | — | ○ | |
| 3/0 | ○ | — | — | — | — | ○ | |
| 4/0 | ○ | — | — | — | — | — |
○indicates the standard stock color.
* The Y/G line is green with 3 yellow recessed color bands (30% to 50%).
Sales standard strip length
100 m