Molded Case Circuit Breakers (MCCB) NF-SVF Series with accessories

Caution
Product Description
Mitsubishi low-voltage breaker contributing to building the future of electrical equipment.
Mitsubishi No-Fuse Breakers and Earth Leakage Circuit Breakers, meeting the needs of the market for over half a century.
Including the new WS-V series equipped with the latest breaker technology, various product ranges are available that address the needs of both the power incoming panel / distribution board market and machinery market.
MITSUBISHI Circuit Breakers Specifications
| Circuit Breakers Part Number | Circuit Breakers Model NF32-SVF | Circuit Breakers Model NF63-SVF | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Rated Current In Standard Ambient Temperature 40°C A | 3 5 10 15 20 30 | 32 | (3) (5) (10) 15 20 30 40 50 | 60 | (63) | ||||||||
| Number of Positions | 2 | 3 | 2 | 3 | 2 | 3 | 2 | 3 | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 440 | 440 | 440 | 440 | 440 | ||||||||
| Rated Short-Circuit Breaking Capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | - | - | - | - | |||||
| 500 V | - | - | - | - | - | ||||||||
| 440 V | 2.5/2.5 | 2.5/2.5 | 7.5/6 | 7.5/6 | 7.5/6 | ||||||||
| 415 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 400 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 380 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 230 V | 7.5/7.5 | 7.5/7.5 | 15/15 | 15/15 | 15/15 | ||||||||
| DC (*1) | 250 V | - | - | - | - | - | |||||||
| 125 V | 10/10 | 10/10 | 10/10 | 10/10 | 10/10 | ||||||||
| GB 14048.2 (lcu/lcs) | AC | 415 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||
| 400 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 380 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 230 V | 7.5/7.5 | 7.5/7.5 | 15/15 | 15/15 | 15/15 | ||||||||
| DC (*1) | 250 V | - | - | - | - | - | |||||||
| 125 V | 10/10 | 10/10 | 10/10 | 10/10 | 10/10 | ||||||||
| Standard Included Parts (Surface Type) | IEC 35-mm Circuit Breakers Rail Mounting Clip (*2) Insulation Barriers (2 Positions 2 Plates, 3 Positions 4 Plates) | ||||||||||||
*(1) For 3-position Circuit Breakers, use 2 positions.
(2) Only compatible with NF63-SVF 60A and 63A.
Note (1) Mounting screws must be prepared by the customer (recommended size: M4 × 0.7 × 65 [2 pieces])
| Circuit Breakers Part Number | Circuit Breakers Model NF125-SVF | ||||||
|---|---|---|---|---|---|---|---|
| Rated Current In Standard Ambient Temperature for Circuit Breakers 40°C A | 15 20 30 40 50 60 75 100 | 125 | |||||
| Number of Positions | 2 | 3 | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 600 | 600 | |||||
| Rated Short-Circuit Breaking Capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | - | ||
| 500 V | 10/10 | 10/10 | |||||
| 440 V | 20/20 | 20/20 | |||||
| 415 V | 25/25 | 25/25 | |||||
| 400 V | 25/25 | 25/25 | |||||
| 380 V | 25/25 | 25/25 | |||||
| 230 V | 50/50 | 50/50 | |||||
| DC (*1) | 250 V | - | - | ||||
| 125 V | 15/15 | 15/15 | |||||
| GB 14048.2 (lcu/lcs) | AC | 415 V | 25/25 | 25/25 | |||
| 400 V | 25/25 | 25/25 | |||||
| 380 V | 25/25 | 25/25 | |||||
| 230 V | 50/50 | 50/50 | |||||
| DC (*1) | 250 V | - | - | ||||
| 125 V | 15/15 | 15/15 | |||||
| Standard Included Parts (Surface Type) | IEC 35-mm Circuit Breakers Rail Mounting Clip Insulation Barriers (2 Positions 1 Piece, 3 Positions 2 Pieces) M4 × 0.7 × 55 Mounting Screws (2 Pieces) | ||||||
*(1) For 3-position Circuit Breakers, use 2 positions.
Drawing Showing Dimensions of MITSUBISHI Circuit Breakers

Circuit Breakers Model NF32-SVF・NF63-SVF
Surface Type
Note (1) Direct cable connection is not possible.
(2) Motor breakers only have 3 positions.

Circuit Breakers Model NF125-SVF
Surface Type
Note (1) The 2-position product of NF125-SVF is the product where the middle pole of the 3-pole breaker is removed.