Bus node, CPX Series

Brand :
FESTO
Caution
Product Description
Bus node, CPX Series

CPX-FB36

CPX-FB13

CPX-M-FB34
Specifications
| Type | CPX-FB36 | ||
|---|---|---|---|
| Fieldbus interface | 2x M12x1 socket, D-coded, 4-pin | ||
| Baud rates [Mbit/s] | 10/100 | ||
| Protocol | EtherNet/IP | ||
| Modbus TCP | |||
| Max. address capacity, inputs [byte] | 64 | ||
| Max. address capacity, outputs[byte] | 64 | ||
| LED displays (bus-specific) | MS NS TP1 TP2 | = Module status = Network status = Network active port 1 = Network active port 2 | |
| Device-specific diagnostics | Module and channel-oriented diagnostics Module undervoltage Diagnostic memory | ||
| Configuration support | EDS file L5K export with CPX-FMT | ||
| Parameterisation | Diagnostic behaviour Fail-safe response Forcing of channels Idle mode characteristics Signal setup System parameters | ||
| Additional functions | EtherNet/IP Quickconnect Ring topology (DLR) Acyclic data access via "Explicit Message" and Ethernet Integrated switch IP addressing via DHCP, DIL switch or operator unit Channel-oriented diagnostics via fieldbus Start-up parameterisation in plain text via fieldbus System status can be represented using process data Additional diagnostic interface for operator units | ||
| Control elements | DIL switches | ||
| Operating voltage | Nominal value [V DC] | 24 | |
| Permissible range [V DC] | 18 to 30 | ||
| Current consumption (at nominal voltage) [mA] | Typically 100 | ||
| Protection class to EN 60529 | IP65, IP67 | ||
| Temperature range | Operation [℃] | -5 to +50 | |
| Storage/transport [℃] | -20 to +70 | ||
| Materials | PA reinforced | ||
| Note on materials | RoHS-compliant | ||
| Grid dimension [mm] | 50 | ||
| Dimensions (incl. interlinking block) W x L x H [mm] | 50 x 107 x 50 | ||
| Product weight [g] | 125 | ||
| Type | CPX-FB13 | |
|---|---|---|
| Fieldbus interface | Sub-D socket, 9-pin (EN 50 170) Galvanically isolated 5 V | |
| Baud rate [Mbit/s] | 0.0096 to 12 | |
| Addressing range | 1 to 125 Set using DIL switch | |
| Product range | 4: Valves | |
| Ident. number | 0x059E | |
| Communication types | DPV0: Synchronous communication DPV1: Asynchronous communication | |
| Configuration support | GSD file and bitmaps | |
| Max. address capacity | Inputs [byte] | 64 |
| Outputs [byte] | 64 | |
| LED displays (bus-specific) | BF: Bus fault | |
| Device-specific diagnostics | Identifier and channel-oriented diagnostics EN 50170 (PROFIBUS standard) | |
| Parameterisation | Start-up parameterisation via configuration interface in plain text (GSD) Asynchronous parameterisation via DPV1 | |
| Additional functions | Storage of the last 40 errors with timestamp (access via DPV1) 8-bit system status in image table for inputs 2-byte inputs and 2-byte outputs, system diagnostics in image table | |
| Control elements | DIL switch | |
| Operating voltage | Nominal value [V DC] | 24 |
| Permissible range [V DC] | 18 to 30 | |
| Power failure buffering [ms] | 10 | |
| Current consumption | Typically 200 | |
| Protection class to EN 60529 | IP65, IP67 | |
| Temperature range | Operation | -5 to +50 |
| Storage/transport | -20 to +70 | |
| Materials | PA-reinforced PC | |
| Grid dimension | 50 | |
| Dimensions (incl. interlinking block) W x L x H | 50 x 107 x 50 | |
| Weight | 115 | |
| Type | CPX-M-FB34 | ||
|---|---|---|---|
| Fieldbus interface | 2x RJ45 push-pull socket, AIDA | ||
| Baud rate [Mbit/s] | 100 | ||
| Protocol | PROFINET RT | ||
| PROFINET IRT | |||
| Max. address capacity | Inputs [byte] | 64 | |
| Outputs [byte] | 64 | ||
| LED displays | (bus-specific) | M/P NF TP1 TP2 | = Maintenance/PROFIenergy = Network fault = Network active port 1 = Network active port 2 |
| (product-specific) | M PL PS SF | = Modify, parameterisation = Load supply = Electronic supply, sensor supply = System fault | |
| Device-specific diagnostics | Channel and module-oriented diagnostics Undervoltage of modules Diagnostic memory | ||
| Configuration support | GSDML file | ||
| Parameterisation | System parameters Diagnostic behaviour Signal setup Fail-safe response Forcing of channels | ||
| Additional functions | Start-up parameterisation in plain text via fieldbus Fast startup (FSU) Channel-oriented diagnostics via fieldbus Asynchronous data access via fieldbus and via Ethernet System status can be represented using process data Additional diagnostic interface for operator units | ||
| Control elements | DIL switch, optional memory card | ||
| Operating voltage | Nominal value [V DC] | 24 | |
| Permissible range [V DC] | 18 to 30 | ||
| Intrinsic current consumption at nominal operating voltage [mA] | Typically 120 | ||
| Protection class to EN 60529 | IP65, IP67 | ||
| Temperature range | Operation [℃] | - 5 to +50 | |
| Storage/transport [℃] | -20 to +70 | ||
| Material of housing | Die-cast aluminium | ||
| Grid dimension [mm] | 50 | ||
| Dimensions (incl. interlinking block) W x L x H [mm] | 50 x 107 x 80 | ||
| Weight [g] | 280 | ||